Landlord smoke alarm requirements and carbon monoxide rules
By TenancyDesk · Sources checked
Landlords in England must fit a smoke alarm on every floor that has a room people live in, and a carbon monoxide alarm in any such room with a fixed fuel-burning appliance, such as a boiler or wood burner. Gas cookers do not count. Check every alarm on the day a new tenancy starts. The fine is up to £5,000.
- Smoke alarms
- One on every floor with living space
- Carbon monoxide alarms
- Every room with a fixed fuel-burning appliance
- Not counted
- Gas cookers
- Testing
- On the day a new tenancy starts
- Faulty alarms
- Fixed as soon as reasonably practicable
- Maximum penalty
- £5,000
What are the smoke alarm regulations for landlords?
The Smoke and Carbon Monoxide Alarm (England) Regulations 2015 give landlords three jobs: fit the right alarms, check they work on the day a new tenancy starts, and repair or replace an alarm when a tenant reports a fault. The rules were updated in 2022, and the new version has applied since 1 October 2022.
The 2022 changes did two main things. They widened the carbon monoxide rule from solid fuel appliances, such as coal and wood burners, to any fixed appliance that burns fuel, except gas cookers. And they added the duty to repair or replace an alarm once you are told it is faulty. They also brought social housing into the rules.
These are the rules for England. Scotland, Wales and Northern Ireland set their own.
Sources: GOV.UK: Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022, guidance for landlords and tenants · Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4
How many smoke alarms does a rented home need, and where?
At least one on every floor that has a room used, even partly, as living space. The rules count a bathroom or toilet as living space, and a hall or landing as a room. So a floor with only a bathroom on it still needs a smoke alarm.
In practice a flat on one level needs at least one, a two-storey house at least two, and a three-storey house with a bedroom or bathroom on the top floor at least three. One per floor is the legal minimum. A large floor, or one with closed doors between the alarm and the bedrooms, may need more so the alarm can be heard.
The rules do not say where on the floor the alarm must go. The government’s guidance says smoke alarms should usually go on the ceiling in a hall or landing, and that you should follow the maker’s instructions.
A heat detector does not count. The guidance says heat detectors are not a replacement for smoke alarms.
Sources: Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4 · GOV.UK: Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022, guidance for landlords and tenants
Do landlords have to fit carbon monoxide alarms?
Yes, in any room used as living space that has a fixed appliance burning fuel, other than a gas cooker. The guidance describes this as fixed equipment where fuel of any type is burned to make heat, and gives gas or oil boilers and log-burning stoves as examples.
So a room with a gas boiler, gas fire, oil boiler or wood burner needs a carbon monoxide alarm. A kitchen with a gas cooker and nothing else that burns fuel does not, though you can still fit one. Remember a bathroom or hallway counts as a room, so a boiler in a cupboard off the landing means the landing needs an alarm.
The test is whether the appliance is fixed and burns fuel. Electric heaters, showers and cookers burn nothing, so they do not count. An open fire the tenant can use does burn fuel, so the safe choice is to fit an alarm in that room. The guidance says a fireplace that is only for show and cannot be used does not count.
The guidance says a carbon monoxide alarm should usually be at head height, on a wall or shelf, about 1 to 3 metres from the appliance. A boiler or fire also needs a yearly gas check: see what a gas safety certificate costs.
Sources: Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4 · GOV.UK: Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022, guidance for landlords and tenants
Do landlords have to test smoke alarms?
Yes, on the day a new tenancy starts. You must make sure every required alarm works that day. The tenancy starts on the day the tenant is entitled to move in under the agreement, which may not be the day they collect the keys.
It is up to you to keep a record of when the alarms were tested. The guidance suggests one way: go through the inventory with the tenant on the first day and ask them to sign it to confirm the alarms were tested and work. A renewal with the same tenant for the same home is not a new tenancy, so it does not need a fresh day-one check.
If a letting agent does the check-in, the duty is still yours. Tell the agent the alarms must be tested on the first day, and ask for the signed inventory page so you hold the record yourself. The guidance also suggests showing tenants how, and how often, to test their alarms, and giving them the maker’s instructions.
- Walk round floor by floor and note each smoke alarm, including floors with only a bathroom or a landing.
- List every boiler, fire, stove and other fuel-burning appliance, and check there is a carbon monoxide alarm in each of those rooms.
- Press the test button on every alarm on the day the tenancy starts, not the week before.
- Write the date, the alarms tested and the result on the inventory, and ask the tenant to sign it.
- Check the replace-by date printed on each alarm and note the earliest one.
- Keep the signed record with the tenancy documents. Our landlord certificates checklist lists what else to hand over at the start.
Sources: Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4 · GOV.UK: Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022, guidance for landlords and tenants
TenancyDesk records the alarm test for each new tenancy. Start the free trial
Who fixes a faulty smoke alarm in a rented home?
The landlord. Once a tenant tells you an alarm may not be working, and it is found not to work, you must repair or replace it. The rules give no set number of days. It must be done as soon as reasonably practicable.
During the tenancy, the guidance says tenants should test their alarms and change the batteries where the alarm has replaceable ones. If it still does not work with new batteries, or the tenant cannot change them, they should tell you, and it is yours to fix.
If a tenant will not let you in to fit or fix an alarm, you must take all reasonable steps, but you do not have to go to court to get in. Write to explain that the alarm is a legal requirement and for their safety, offer a time that suits them, and keep a written note of every attempt.
Tell tenants in writing how to report a faulty alarm, and note each report and the date you fixed it. That note is your evidence if the council asks.
Sources: Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4 · Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, Part 3 (remedial notices) · GOV.UK: Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022, guidance for landlords and tenants
Do smoke alarms in a rental have to be hard-wired?
No. The rules do not say what type of alarm to fit, and they do not require mains-wired (hard-wired) alarms. The guidance says to choose alarms that suit the building and the tenants. Smoke alarms should meet British Standard BS 5839-6 and carbon monoxide alarms BS EN 50291.
If you choose battery alarms, the guidance says ones with ‘sealed for life’ batteries are better than ones with replaceable batteries. Mains alarms are part of the fixed wiring, so they are covered by the electrical inspection described in our guide to EICR costs.
Think about who lives there. The guidance says a tenant who is deaf or hard of hearing may need alarms that flash or vibrate. Whatever you choose, fit it where the maker’s instructions say and keep the instructions with the property’s papers. An alarm in the wrong place, or past the replace-by date printed on it, may sound when tested and still not protect the tenant.
Which tenancies do the alarm rules cover?
Most private rented homes and social housing in England. The guidance lists the lets that are not covered: a home shared with the landlord or the landlord’s family, long leases, student halls, hotels and refuges, care homes, hospitals and hospices, low-cost ownership homes and other healthcare accommodation. The rules do not apply to owner occupiers.
A live-in landlord counts as sharing if the tenant shares a kitchen or living room with them or their family, and then the rules do not apply.
Licensed houses in multiple occupation (HMOs) are not covered by this part of the rules, because similar alarm conditions are written into the licence instead. If you let a shared house, see our HMO licence guide to find out which rules apply to you.
What is the fine for not having smoke alarms?
Up to £5,000. The local council enforces the rules, and it does not fine straight away. If it has good reason to think a landlord is breaking the rules, it must first serve a remedial notice: a notice telling you what to put right. The fine is for not doing what that notice says.
The council decides the amount, up to £5,000, and must be satisfied on the balance of probabilities that you did not do what the notice required. The guidance says fines are per breach, not per landlord or per property, so a landlord can face more than one.
The table shows the time limits in the rules. You can appeal a fine to the First-tier Tribunal. Alarms are one of several safety jobs, listed in our checklist for becoming a landlord. TenancyDesk records the day-one alarm check for each tenancy.
| Step | Time limit |
|---|---|
| Council serves a remedial notice | Within 21 days of deciding it has good reason |
| Landlord does what the notice says | Within 28 days of the notice being served |
| Landlord objects in writing | Within 28 days; the notice is on hold while the council looks at it |
| Council arranges the work itself, with the occupier’s agreement | Within 28 days of being satisfied the landlord is in breach |
| Council serves a penalty charge notice | Within 6 weeks of being satisfied of the breach; maximum £5,000 |
Sources: Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, Part 3 (remedial notices) · Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 8 (penalty charge) · GOV.UK: Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022, guidance for landlords and tenants
Common questions
Do landlords have to provide smoke alarms?
Yes. Landlords in England must fit at least one smoke alarm on every floor that has a room used as living space, and bathrooms, halls and landings count. The alarms must be checked on the day a new tenancy starts, and the council can charge a penalty of up to £5,000 if a remedial notice is ignored.
Does a landlord need a carbon monoxide alarm for a gas boiler?
Yes. Since 1 October 2022 a carbon monoxide alarm is needed in any room used as living space that has a fixed appliance burning fuel, other than a gas cooker. The government’s guidance names gas and oil boilers as examples. If the boiler is in a kitchen, bathroom, bedroom or hallway, that room needs an alarm.
Is a carbon monoxide alarm needed for a gas hob or cooker?
No. Gas cookers are the one exception in the rules: a room needs a carbon monoxide alarm if it has a fixed fuel-burning appliance other than a gas cooker. A kitchen with a gas cooker and a gas boiler does need one, because of the boiler. You can always fit an alarm where it is not required.
Who is responsible for testing smoke alarms in a rented property?
The landlord must check that every required alarm works on the day a new tenancy starts. After that, the government’s guidance says tenants should test their alarms and change batteries. If an alarm is reported as faulty and is found not to work, the landlord must repair or replace it as soon as reasonably practicable.
Do smoke alarms in rented properties have to be mains wired?
No. The rules do not require mains-wired alarms. The government’s guidance says to choose alarms that suit the building and the tenants, that smoke alarms should meet BS 5839-6, and that battery alarms with sealed-for-life batteries are the better option. A licensed HMO may have stricter conditions in its licence.
What if my tenant will not let me in to fit an alarm?
You must take all reasonable steps, but you do not have to go to court to get in. The government’s guidance says to write to the tenant explaining that the alarm is a legal requirement and for their safety, offer a time that suits them, and keep a written record of every attempt to show the council if asked.
What is the fine for not having smoke alarms in a rented property?
Up to £5,000. The council must first serve a remedial notice giving the landlord 28 days to put things right. If the landlord does not, the council can arrange the work itself with the occupier’s agreement and charge a penalty of up to £5,000. Fines are per breach, not per landlord or property.
Official sources and scope
Checked on 16 November 2026. This is general information for private landlords in England, not legal advice or a complete compliance assessment. Follow the current official guidance for your tenancy and get advice about exceptions, missed deadlines or disputes.
- GOV.UK: Smoke and Carbon Monoxide Alarm (Amendment) Regulations 2022, guidance for landlords and tenants
- Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 4
- Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, Part 3 (remedial notices)
- Legislation: Smoke and Carbon Monoxide Alarm (England) Regulations 2015, regulation 8 (penalty charge)
Let TenancyDesk do this part for you
It keeps every certificate against its property, reads the dates off the ones you upload, and emails you before each one runs out.
Seven days free. No card needed.